Software controlled charging
curves, ZIVAN checks every parameter of the charging cycle following the
norms coming from the battery manufactures. |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
 |
Charging curve IUIa for all lead batteries
and for gel batteries in the first phase T 1 the current output is
constant at the nominal value, up to the gassification voltage U1 of
2,35 ÷2,4 V/cell. In the second phase T2 Voltage U1 is constant while
current decreases from I 1 to I 2 that is the value requested for the
third phase. This value is constant for the whole third phase up to the
end charge. The different charging phases are visualized by a Led Bar. |
 |
 |
Charging curve IUIUo Floating
The three first phases are identical to those of the IUIa. There is no
stop but an endless phase of controlled constant Voltage U2 of 2,23
V/cell. Is very useful tomaintain the battery fully charged even after
long period of non use. |
 |
 |
|
 |
 |
 |
 |
 |
 |
 |
 |
 |